Re: Online condensate monitoring


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 2 ] [ FAQ ]

Posted by Damien Cullen on August 14, 2002 at 00:19:36:

In Reply to: Re: Online condensate monitoring posted by Joe Lambert on July 15, 2002 at 05:44:42:

A TOC or (Total Organic Carbon) analyser will pick up organics (Glucose, sucrose etc) The fastest response times are around 3 minutes so a buffer tank will be required. These should be used with conductivity monitors which is industry practice in sugar mill boilers to pick up large sugar contaminations (as although conductivity analysers cant detect pure sugars which are non-conductive, there is nearly always organic salts and inorganic acids attached from the dirt and cane which can be detected.

Hope this is of help.