[an error occurred while processing this directive]

Re: Online condensate monitoring


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 2 ] [ FAQ ]

Posted by Joe Lambert on July 15, 2002 at 05:44:42:

In Reply to: Re: Online condensate monitoring posted by Vern on July 12, 2002 at 21:11:06:

Unfortunately, Glucose will not be picked up by a TDS monitor because it is an organic. I ran into this problem in a sugar refinery, the boiler turning into a huge cotton candy maker. The best we could do is hook up an on-line turbidity monitor because the burnt sugar was black, although this did not prevent the initial contamination, it did help. A company called GESTRA makes both turbidity and conductivity monitors specifically for condensate.


Follow Ups:



Post a Followup

Name:
E-Mail:

Subject:

Comments:


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 2 ] [ FAQ ]