These diagrams are for general information only. Consult Boilerroom.com
for individual, detailed installation instructions.
Economizer installation for non-dearated boiler feedwater. Unit design specifics:
Duplex stainless steel economizer tubes with stainless steel fins are required due to dissolved
oxygen in the water. Upgrade to Duplex stainless steel required to prevent against chloride stress corrosion cracking
of any 300 series stainless steel tube.
Installation adequate for natural gas firing and #2 oil firing
Any economizer that is installed in a possible condensing application MUST
be designed with provisions in the lower transition to collect and drain all
condensation from the stack, preventing it from entering and damaging the boiler.
Economizer Installation for Non-Deaerated Feedwater Entering Boiler
Utilizing Continuous Running Feedpumps with Modulating Feedvalve:
During normal operation the boiler feedpump sends the feedwater through
the economizer, modulating feedvalve, and into the boiler.
When the feedvalve is completely shut, a small recirculation line
back to the tank is required to maintain flow in the economizer to avoid a
stagnant flow situation. A stagnant flow situation will lead to economizer
steaming and hammering, possibly leading to economizer and boiler damage.
Contact factory for recirculation line size requirements.