[an error occurred while processing this directive]

Re: TWO STEAM BOILERS WITH DIFFERENT MAWP


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 4 ] [ FAQ ]

Posted by Steve on April 08, 2011 at 13:21:05:

In Reply to: TWO STEAM BOILERS WITH DIFFERENT MAWP posted by ROY REYES on December 14, 2010 at 14:05:39:

ASME section I states that if multiple boilers on a common header vary more than 6% in MAWP, additional overpressure protection must be provided on the lower pressure unit.


Follow Ups:



Post a Followup

Name:
E-Mail:

Subject:

Comments:


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 4 ] [ FAQ ]