[an error occurred while processing this directive]

Re: McDonnel Miller


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 3 ] [ FAQ ]

Posted by yodaddy on January 07, 2004 at 22:08:03:

In Reply to: McDonnel Miller posted by Manny on January 07, 2004 at 15:41:09:

See if there is a quick opening type valve installed on the float blowdown....if so, swap in a standard globe valve.

Many folks have installed 1/4 turn ball valves cause they are cheap and reliable. Those type valves allow the operator to damage the floats just like you described.