Posted by Raymond on February 24, 2002 at 14:23:25:
In Reply to: High silica content ! posted by Ramesh R on February 18, 2002 at 19:46:06:
: im having high silica content in my raw water (20 ppm)& in boiler water reading is about 300ppm.Is there any way i can reduce silica content in boiler water to prevent silica scales?what is the permittable amount of silica content in boiler water?
The silica limits we run our boilers at are:
boilers operating at 14 barg pressure < 30 ppm.
Boilers operating at 70 barg pressure < 6 ppm
they all have turbines running downstream.
Apart from that I backup the views of Vern and Joe