Re: Deaerator vent spewing water slugs


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 2 ] [ FAQ ]

Posted by Jim on November 15, 2001 at 06:52:09:

In Reply to: Deaerator vent spewing water slugs posted by George Larose on November 09, 2001 at 18:38:56:

We have had this problem with a lockwood DA. It happens when a large load swing occurs in our 100% make up. The steam pressure gets hauled down a bit and the water condenses the steam causing pockets of steam trapped in the water usually accompanied by a rumbling or shaking of the Da platform. We cut a couple slots in the internal of the steam distrubition pipe to help balance the steam in the storage section and the scrubbing section. {SUGGESTED BY MANUFACTURER} it has worked fine with no adverse affects on the DA performance.

Jim