Re: CO


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 2 ] [ FAQ ]

Posted by Tim Hodgson on April 23, 2000 at 21:05:28:

In Reply to: CO posted by Rich on April 19, 2000 at 09:56:13:

: What are the maximum flue gas CO levels that should be allowed while firing on #6 oil?

What type of burner and boiler do you have? Your Authority having Jusidiction may have some local codes that address this issue. Myself, I would try to get it below 40ppm if it is steam atomized and below 200 ppm if it is a rotary cup burner.