We also were going through uv units. They do get pricy...


[ Follow Ups ] [ Post Followup ] [ Boilerroom.com Steam-Forum - Number 2 ] [ FAQ ]

Posted by MikeH on May 02, 2001 at 20:37:58:

In Reply to: Re: honeywell7800seriesburnercontrol posted by mike on May 02, 2001 at 15:26:04:

It turned out that ours were installed wrong. Instructions said to never run the signel lines parallel to power lines. We also thought they might be over heating, since the units sit right in front of the burner face. We installed cooling fans above the front of the burners. We still lose one now and then, but certainly not like we were a couple years ago.