Posted by Dam on November 26, 2010 at 18:48:51:
In Reply to: Re: Slow drip from relief valve posted by HeatPro on November 21, 2010 at 22:47:17:
: Either that gauge is wrong or the relief valve is wrong.
Thanks HeatPro. I installed another pressure gauge right before the relief valve and it read the same as my other one did with 1 pound of pressure. I therefore took the new relief valve back and exchanged it which solved the problem. Surprised that a new relief valve would be defective given that it is a safety device but that appears to be the case.