Posted by HeatPro on October 14, 2009 at 09:18:34:
In Reply to: Re: Short cycle time on gas steam boiler posted by jeff on October 14, 2009 at 07:47:22:
: : First, check that the thermostat anticipator is not below 0.2 setting. Set too low, the anticipator heats the bimetal too fast and disconnects the burner to cool down and restart fast.
: >> Is this anticipator in the wall thermostat or something on the furnace?
Yes, it is the wall thermostat to check.
http://www.heatpro.us/service/anticipator.htm