Posted by HeatPro on March 05, 2007 at 22:39:18:
In Reply to: LWCO constant failure posted by Jon Held on March 05, 2007 at 16:38:17:
The failure is from insistence on not hand-draining the system once a week by using a float. Blow the mud once per week from the boiler, sight glass and float - no problem. No float, no auto feed, no problem. You have to descale the float every few months to prevent overloading it.