Posted by Jack, CVMS on November 08, 2005 at 01:17:21:
In Reply to: Weil Mclain 468 oil fired burner posted by Kevin Horrigan on November 03, 2005 at 14:03:30:
: I'm trying to determine what the BTu/hr rating is for this boiler. The emergency shut off was installed directly over the ID plate.
: I can see that the unit design rate is 1.25 gal per hour.
: It is currently equipped with a Riello Burner (4E?), don't know the nozzle size.
When they had a Beckett burner installed on them it was with a 1.25 x 80° @ 100 psi. The Riello probably had a different setup, but with the same fuel delivery.