Posted by HeatPro on December 04, 2004 at 20:30:02:
In Reply to: steam boiler leak posted by Jane on December 04, 2004 at 17:56:42:
A sight glass drip isn't enough to make you have to add water every day; but a leak at the water line could. Fill the boiler to the top of the glass to see if water comes out of a hole just at the water line to run out on the floor.
If you are comfortable removing the sight glass, unscrewing the sight glass fitting and retightening, then it is doable by a DIY.