The most likely cause is a lack of a flow control (weighted check valve0 on the line from the radiant loop circulator. The other pumps force water backwards against the pump without a check valve.
http://64.226.150.132/hydronic/multcirc/multcirc.htm
Another cause would be using a high-head pump (over 11 feet head), which is unnecessary.